Description
1. Basic Information
表格
| Item | Content |
|---|---|
| Model | T9432 (Standard); Conformal coated variant:T9432C |
| Series | AADvance TMR Safety‑Instrumented System |
| Product Type | 16‑Channel Isolated Analogue Input Module |
| Safety Certification | IEC 61508 SIL‑3, TÜV certified |
| Chassis | AADvance standard chassis, hot‑swap slot |
| Matching FTA | AADvance dedicated analogue FTA terminal unit;不兼容 T8000 T88xx 系列端子板 |
| Manufacturer | ICS‑Triplex (Rockwell Automation) |
| Warranty | 12‑month factory standard warranty |
| BOM Full‑Name | T9432, AADvance 16‑Ch Isolated Analogue Input Module |
| BOM Short‑Name | T9432‑Analogue Input Module,16‑Ch,4‑20mA |
2. Electrical Specifications
- Channel count:16 galvanically isolated analogue input channels
- Input signal:4‑20 mA loop powered;measurement range 0‑24 mA;support HART protocol (HART‑5)Rockwell A…
- Resolution:15‑bit
- Accuracy:±0.05 mA @25℃
- Channel‑to‑backplane isolation:1500 VDC(1 min withstand)
- Backplane supply:18‑32 VDC;typical power consumption 4.0 W
- Diagnostics:Per‑channel fault detection;loop break / under‑range / over‑range monitoring;front‑panel per‑channel LED status indicator
- Hot‑swap:Module hot‑swappable;no system trip during replacement
- Architecture:Works with AADvance TMR processor T9110 / T9110C;supports simplex, dual or TMR voting I/O group configuration
3. Environmental Conditions
- Operating temperature:0 ℃ ~ +60 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Humidity:5‑95 % RH, non‑condensing
- Enclosure rating:IP20 (cabinet‑mount installation only)
- Conformal coating:T9432C = full‑PCB conformal coating(G3 offshore grade) for salt‑mist / corrosive atmosphere. Firmware segregated between standard and C‑version.
- Approvals:CE, UL, ATEX, IECEx, SIL‑3 certified.
- Mechanical:166 mm × 42 mm × 118 mm;Weight 340 g
4. Main Functions
- 16‑channel isolated 4‑20 mA analogue signal acquisition: Interface for pressure, level, flow, gas‑detector transmitters in safety‑critical loops; supports HART‑5 to read additional device diagnostic dataRockwell A…。
- Per‑channel LED indication for channel status and fault diagnosis for fast on‑site troubleshooting.
- Comprehensive loop diagnostics: detect open‑loop, under‑range, over‑range fault conditions; fault events time‑stamped for SOE.
- Hot‑swap capability: replace module online without shutting‑down safety logic.
- Flexible I/O redundancy configuration: simplex / dual / TMR voting I/O groups configured via AADvance Workbench software.
- Only interoperable with AADvance platform (T9110/T9110C processor), cannot work with Trusted T8000 T84xx / T88xx hardware.
Related AADvance analogue I/O reference|Part No.|Description|Remark|
|—|—|—|
|T9431|8‑Ch Analogue Input Module|8‑channel 4‑20 mA AI|
|T9432|16‑Ch Analogue Input Module|16‑channel 4‑20 mA AI, with HART|
|T9432C|16‑Ch Analogue Input Module, Conformal Coated|Off‑shore / high‑corrosion environment|
5. Typical Applications
- On‑shore / offshore SIS‑ESD emergency shutdown system for process analogue variable acquisition.
- Fire & Gas safety system for multi‑point gas‑detector 4‑20 mA signal input.
- Petrochemical, power‑plant safety‑critical pressure, level, flow monitoring loops.
6. Important Notes
- T9432 belongs to AADvance platform, not Trusted T8000. Incompatible with T8000 series cards and T88xx FTA terminals. Must pair with AADvance dedicated analogue FTA.
- Two variants available: T9432(standard), T9432C(conformal coated offshore version). Firmware cannot be cross‑loaded.
- Support simplex, dual redundant or TMR voting I/O groups configured via AADvance Workbench software.
- Hot‑swap operation permitted; install only inside certified safety cabinet, not for direct hazardous‑zone mounting.
- HART data is secondary diagnostic information, safety logic shall use 4‑20 mA analogue value.








Reviews
There are no reviews yet.