ICS T9432, AADvance 16‑Channel Isolated 4‑20mA Analogue Input Module with HART

T9432 is 16‑channel galvanically‑isolated 4‑20 mA analogue input module with HART‑5 support for ICS Triplex AADvance SIL‑3 safety‑instrumented system. Provides multi‑point safety‑loop transmitter signal acquisition with per‑channel loop diagnostics and hot‑swap support. T9432C conformal‑coated variant is available for offshore salt‑mist applications. Used for ESD and Fire&Gas multi‑point process‑variable monitoring.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

1. Basic Information

表格
Item Content
Model T9432 (Standard); Conformal coated variant:T9432C
Series AADvance TMR Safety‑Instrumented System
Product Type 16‑Channel Isolated Analogue Input Module
Safety Certification IEC 61508 SIL‑3, TÜV certified
Chassis AADvance standard chassis, hot‑swap slot
Matching FTA AADvance dedicated analogue FTA terminal unit;不兼容 T8000 T88xx 系列端子板
Manufacturer ICS‑Triplex (Rockwell Automation)
Warranty 12‑month factory standard warranty
BOM Full‑Name T9432, AADvance 16‑Ch Isolated Analogue Input Module
BOM Short‑Name T9432‑Analogue Input Module,16‑Ch,4‑20mA

2. Electrical Specifications

  • Channel count:16 galvanically isolated analogue input channels
  • Input signal:4‑20 mA loop powered;measurement range 0‑24 mA;support HART protocol (HART‑5)Rockwell A…
  • Resolution:15‑bit
  • Accuracy:±0.05 mA @25℃
  • Channel‑to‑backplane isolation:1500 VDC(1 min withstand)
  • Backplane supply:18‑32 VDC;typical power consumption 4.0 W
  • Diagnostics:Per‑channel fault detection;loop break / under‑range / over‑range monitoring;front‑panel per‑channel LED status indicator
  • Hot‑swap:Module hot‑swappable;no system trip during replacement
  • Architecture:Works with AADvance TMR processor T9110 / T9110C;supports simplex, dual or TMR voting I/O group configuration

3. Environmental Conditions

  • Operating temperature:0 ℃ ~ +60 ℃
  • Storage temperature:‑40 ℃ ~ +85 ℃
  • Humidity:5‑95 % RH, non‑condensing
  • Enclosure rating:IP20 (cabinet‑mount installation only)
  • Conformal coating:T9432C = full‑PCB conformal coating(G3 offshore grade) for salt‑mist / corrosive atmosphere. Firmware segregated between standard and C‑version.
  • Approvals:CE, UL, ATEX, IECEx, SIL‑3 certified.
  • Mechanical:166 mm × 42 mm × 118 mm;Weight 340 g

4. Main Functions

  1. 16‑channel isolated 4‑20 mA analogue signal acquisition: Interface for pressure, level, flow, gas‑detector transmitters in safety‑critical loops; supports HART‑5 to read additional device diagnostic dataRockwell A…。
  2. Per‑channel LED indication for channel status and fault diagnosis for fast on‑site troubleshooting.
  3. Comprehensive loop diagnostics: detect open‑loop, under‑range, over‑range fault conditions; fault events time‑stamped for SOE.
  4. Hot‑swap capability: replace module online without shutting‑down safety logic.
  5. Flexible I/O redundancy configuration: simplex / dual / TMR voting I/O groups configured via AADvance Workbench software.
  6. Only interoperable with AADvance platform (T9110/T9110C processor), cannot work with Trusted T8000 T84xx / T88xx hardware.
Related AADvance analogue I/O reference

|Part No.|Description|Remark|

|—|—|—|

|T9431|8‑Ch Analogue Input Module|8‑channel 4‑20 mA AI|

|T9432|16‑Ch Analogue Input Module|16‑channel 4‑20 mA AI, with HART|

|T9432C|16‑Ch Analogue Input Module, Conformal Coated|Off‑shore / high‑corrosion environment|

5. Typical Applications

  1. On‑shore / offshore SIS‑ESD emergency shutdown system for process analogue variable acquisition.
  2. Fire & Gas safety system for multi‑point gas‑detector 4‑20 mA signal input.
  3. Petrochemical, power‑plant safety‑critical pressure, level, flow monitoring loops.

6. Important Notes

  1. T9432 belongs to AADvance platform, not Trusted T8000. Incompatible with T8000 series cards and T88xx FTA terminals. Must pair with AADvance dedicated analogue FTA.
  2. Two variants available: T9432(standard), T9432C(conformal coated offshore version). Firmware cannot be cross‑loaded.
  3. Support simplex, dual redundant or TMR voting I/O groups configured via AADvance Workbench software.
  4. Hot‑swap operation permitted; install only inside certified safety cabinet, not for direct hazardous‑zone mounting.
  5. HART data is secondary diagnostic information, safety logic shall use 4‑20 mA analogue value.

Reviews

There are no reviews yet.

Be the first to review “ICS T9432, AADvance 16‑Channel Isolated 4‑20mA Analogue Input Module with HART”

Your email address will not be published. Required fields are marked *