Description
Hardware & Electrical Specifications
- Model:PU516
- Part Number:3BSE013064R1
- Module Type:Real‑Time Accelerator (RTA) PCI Board
- Bus Interface:32‑bit PCI 33 MHz, only support 5V PCI signaling
- On‑board Memory:16 MB RAM for real‑time data buffering
- Communication Ports:1×15‑pin D‑Sub MB300 bus port; 1×DB9 RS‑232 serial debug port
- Max bus speed:10000 kbit/s for MB300
- Power supply:Supplied via PCI slot
- Max power consumption:11 W
- Galvanic isolation:≥2000 V AC between field bus side and PCI host side
- Dielectric strength:2000 V AC 1 minute
- Insulation resistance:>100 MΩ @ 500 V DC
- On‑board protection:ESD protection, transient surge suppression, hardware watchdog, conformal coated PCB
- Compatibility note: Can be upgraded to PU516A; PU516 cannot work in 3.3V‑only PCI slot; driver and firmware must match Advant OCS software release; single MB300 channel, no redundant bus channel support.
Environmental Specifications
- Operating temperature:0 ℃ ~ +60 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Protection degree:Installed inside industrial workstation chassis
- EMC compliance:IEC 61000‑6‑2 industrial electromagnetic immunity standard
- Certifications:CE
Mechanical Data
- Installation:Standard full‑length PCI long‑card, insert into 5V PCI slot of Advant workstation
- Interfaces:PCI gold‑finger edge connector; 1×15‑pin D‑Sub female for MB300; 1×DB9 RS‑232
- Suitable wire cross‑section:0.75 mm²‑2.5 mm² copper cable for signal terminals
- Terminal tightening torque:0.6‑1.0 N·m
- Dimension:Standard full‑length PCI card
- Weight:approx 0.40 kg
Main Functions
- Real‑time task off‑loading: Off‑load time‑critical real‑time processing tasks from workstation host CPU, provide deterministic low‑latency processing for Advant OCS DCS system.
- Single‑channel MB300 fieldbus communication: Realize bidirectional high‑speed data exchange between workstation and field controllers via MB300 bus, not support dual‑channel bus redundancy.
- Real‑time data buffering: On‑board 16 MB RAM buffers bus I/O data, alarm and event messages, avoid data loss under high‑load operating condition.
- Hardware‑accelerated MB300 protocol processing: Process MB300 bus protocol on board, reduce host CPU overhead.
- Local serial diagnosis: RS‑232 port supports local board‑level debugging and diagnostic maintenance.
- Board‑level self‑diagnosis: Monitor PCI bus status, MB300 channel status, on‑board power and watchdog circuit; report hardware failure and communication fault to Advant OCS system.
- On‑board multi‑LED status indication
- Green LED:Board power supply normal, RTA core running healthy
- Yellow LED:MB300 bus communication active
- Red LED:Hardware fault / bus communication failure alarm
Installation & Wiring Requirements
- Power off industrial workstation completely before installation; insert PU516 into available 5V PCI slot, fasten bracket screw firmly. Hot‑swap is strictly forbidden.
- Connect MB300 bus cable to 15‑pin D‑Sub connector; follow MB300 bus wiring specification, install correct terminal resistor at bus end point.
- Workstation chassis protective grounding must comply with ABB Advant OCS system grounding specification to improve anti‑interference performance.
- After replacement, install matched RTA driver and firmware corresponding to Advant OCS software version; verify MB300 bus communication status.
- Replacement note: Cannot be used in pure 3.3V PCI slot; if replace with PU516A, confirm workstation PCI slot supports 3.3V/5V mixed signal, and match whole‑system driver firmware.