Bently 1900-65A-00-00-02-00-01 General‑Purpose Equipment Monitor

1900‑65A‑00‑00‑02‑00‑01 is an obsolete multi‑channel machinery monitor. Compared with 1900‑65A‑00‑00‑01‑00‑00, this variant adds Ethernet Modbus‑TCP interface, while keeping 4 dynamic transducer channels +4 temperature input channels. Supports proximity probe, accelerometer, velocity sensor, RTD / thermocouple signals. Provides configurable Alert/Danger alarms, 4‑20 mA analog outputs, 6 programmable relay contacts, BNC buffered waveform test ports, 200‑piece fault event log buffer. DIN‑rail mounting, non‑hot‑swappable, requires official 1900 configuration software for commissioning, available as surplus‑new / tested used / refurbished spare parts.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware & Electrical Specifications

‑ Manufacturer: Bently Nevada (Baker Hughes) ‑ Compatible System: 1900 series machinery monitoring platform ‑ Functional Type: Multi‑Purpose Machinery Monitor(with Modbus‑TCP Ethernet) ‑ Input Channels:  • 4 configurable dynamic transducer inputs (eddy‑current probe, ICP accelerometer, velocity sensor, tachometer pulse)  • 4 temperature inputs: 2‑/3‑wire RTD, Type E/J/K/T thermocouples ‑ Communication Interfaces: RJ45 Ethernet(Modbus‑TCP)+ RS485 Modbus‑RTU ‑ Analog Output: 4 isolated 4‑20 mA outputs, freely assignable to measurement variables ‑ Relay Output: 6 × SPDT programmable relay contacts for Alert, Danger, module fault ‑ Diagnostics: Transducer open‑circuit / short‑circuit detection; BNC buffered waveform output per channel ‑ Event Storage: 200‑entry timestamp fault event log ‑ Auxiliary Power: 18‑36 VDC wide‑range DC supply ‑ Indicators: Multi‑LED for power, module fault, channel alarm status ‑ Connectors: Removable screw terminal blocks for power, I/O; RJ45 Ethernet; BNC test ports ‑ Mounting: 35 mm DIN‑rail installation ‑ Enclosure: Metal housing, IP20 ‑ Certification: Standard CE, no hazardous‑location approval ‑ Hot‑swap: Non‑hot‑swappable; de‑energize DC power before replacement

Environmental Specifications

‑ Operating Temperature: ‑20 °C ~ +60 °C ‑ Storage Temperature: ‑40 °C ~ +85 °C ‑ Relative Humidity: 5%‑95 % non‑condensing ‑ Vibration & Shock: Complies with API‑670 industrial cabinet EMC standards

Mechanical Data

‑ Weight: approx 1.1 kg

Core Functions

  1. Multi‑parameter signal acquisition: Collect shaft vibration, thrust displacement, housing vibration, rotating speed and bearing‑temperature signals for auxiliary rotating‑machinery condition monitoring.
  2. Two‑level alarm supervision: Configurable Alert / Danger thresholds with adjustable time‑delay; latching / non‑latching relay mode selectable to suppress startup nuisance alarms.
  3. Multiple output interfaces: 4‑20 mA analog outputs send trending data to DCS/PLC; relay contacts output alarm signals to local annunciator.
  4. Dual‑mode digital communication: Modbus‑TCP over Ethernet + Modbus‑RTU over RS485, upload real‑time data and fault logs to plant SCADA / System 1 software.
  5. On‑site troubleshooting: BNC buffered ports output raw transducer waveform for oscilloscope inspection; historical fault records support post‑incident analysis.

Installation, Replacement & Critical Warnings

  1. De‑energize 18‑36 VDC auxiliary power before replacement; unit is non‑hot‑swappable. Isolate field sensor wiring for terminal maintenance.
  2. This suffix variant has built‑in Ethernet Modbus‑TCP; cannot be directly replaced by the no‑Ethernet 01‑suffix version, otherwise Ethernet communication function will be lost.
  3. After hardware replacement, download site‑specific configuration via 1900 configuration software; factory default parameters cannot be used for field operation.
  4. After power‑on, verify LED status, channel reading, 4‑20 mA loop, relay‑alarm action and Modbus‑TCP data communication.
  5. Common failure mode: Ethernet transceiver surge damage, field‑wiring damage to transducer input circuits. Inspect sensor cables and grounding when transducer‑fault alarms trigger.

Reviews

There are no reviews yet.

Be the first to review “Bently 1900-65A-00-00-02-00-01 General‑Purpose Equipment Monitor”

Your email address will not be published. Required fields are marked *