GE IC670ALG230 Field‑Control 8‑Channel Current‑Source Analog Input Module

IC670ALG230 is an analog current‑source input module for GE Fanuc Field‑Control distributed I/O system. It provides 8 single‑ended analog input channels for field 2‑wire / 4‑wire transmitters. Each channel can be software‑configured for 0‑20 mA or 4‑20 mA signal. It works together with BIU (Bus Interface Unit) and communicates over Genius field‑bus, converting process current signals into 12‑bit digital values for host PLC. Supports open‑wire detection under 4‑20 mA mode and over‑range alarm. Equipped with removable screw terminal block for convenient field wiring maintenance. Product status: Obsolete, spare‑part only supply available。

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware & Electrical Specifications

‑ Model:IC670ALG230 ‑ Part Number:IC670ALG230 ‑ Module Type:Field‑Control 8‑Channel Current‑Source Analog Input Module ‑ Mounting:Plug‑in onto Field‑Control BIU base unit, DIN‑rail mounting ‑ BIU backplane power:Max 51 mA drawn from BIU backplane ‑ Field loop power:18‑30 VDC nominal 24 VDC; total module consumption max 210 mA including field loop current ‑ Input channels:8 single‑ended analog input channels, common ground group ‑ Signal range:Software configurable per‑channel: 0‑20 mA (default), 4‑20 mA; absolute max input 30 mA ‑ Resolution:12‑bit digital resolution; analog resolution 5.0 μAQualitrol ‑ Conversion time:Typical 60 μs per channel @1 MHz clockQualitrol ‑ Input impedance:Approx 250 Ω ‑ Filter:On‑board 1st‑order RC filter, typical cutoff frequency 160 Hz ‑ Diagnosis:Open‑wire detection (trigger below 2 mA for 4‑20 mA range); over‑range fault indication above 20 mA ‑ Communication interfaces:Field‑Control backplane to BIU, further to Genius‑bus ‑ Terminal:Removable screw‑clamp terminal block ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:1500 VAC 1‑minute withstand field‑to‑logic isolation; 250 VAC continuous isolation; transient surge suppression; hardware self‑diagnosis ‑ Compatibility note:Cannot run standalone; must match Field‑Control BIU unit; full analog‑loop simulation test mandatory after replacement.

Environmental Specifications

‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification

Mechanical Data

‑ Weight:approx 0.26 kg ‑ Dimension:Standard Field‑Control module form‑factor ‑ Handling note:ESD‑sensitive precision analog circuit, anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m

Main Functions

  1. Collect 4‑20 mA /0‑20 mA current signals from field pressure, flow, level and temperature transmitters.
  2. Perform analog‑to‑digital conversion, transmit digital process values to BIU over local backplane, then upload to Genius‑bus master controller.
  3. Built‑in channel‑level fault diagnosis: open‑loop, over‑range detection, convenient for field‑side troubleshooting.
  4. LED status indication:   ‑ Green OK:Module power‑on and self‑test pass

Installation & Wiring Requirements

  1. Cut off BIU rack power and field 24VDC loop power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling module.
  2. Insert IC670ALG230 fully into Field‑Control BIU base slot and lock firmly.
  3. Analog‑loop wiring strictly follow GE Field‑Control hardware manual GFK‑0893G; use shielded twisted‑pair instrument cable; separate analog signal cables from high‑power cables, connect shielding to dedicated protective ground terminalQualitrol.
  4. Complete protective grounding according to GE system specification.
  5. After replacement: power‑on, verify OK LED status, download module channel configuration, perform full‑channel signal test and fault‑simulation test.
  6. Replacement note: Verify BIU hardware and firmware compatibility; full analog‑loop simulation test mandatory before unit put‑into‑service.