Description
Hardware & Electrical Specifications
‑ Model:IC690RFH008 ‑ Part Number:IC690RFH008 ‑ Module Type:Genius Fiber‑Optic Repeater ‑ Mounting:Panel or 35 mm DIN‑rail mounting, standalone unit ‑ Power supply:18‑30 VDC nominal 24 VDC; typical power consumption 120 mA ‑ Fiber interface:Dual ST‑connector for multi‑mode optical fiber; recommended fiber 62.5/125 µm multi‑mode ‑ Maximum fiber distance:2000 meters under 153.6k baud‑rate; longer distance at lower baud‑rate ‑ Electrical Genius‑bus ports:Two screw‑terminal ports for copper Genius‑bus daisy‑chain wiring ‑ Supported baud‑rate:38.4k /76.8k /153.6k standard /153.6k extended baud‑rate, auto‑detect ‑ Operation mode:Transparent repeater, no Genius‑bus node address ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:Surge suppression on Genius copper bus side; complete galvanic isolation between different bus segments via optical link ‑ Compatibility note:Cannot run standalone; must match Genius‑bus baud‑rate of whole system; install bus terminators at physical ends of each copper bus segment; full Genius‑bus communication test mandatory after replacement。
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight:approx 0.75 kg ‑ Dimension:140 × 85 × 110 mm ‑ Handling note:ESD‑sensitive circuit; avoid direct eye exposure to optical fiber transmit port; anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Genius‑bus signal media converter, converts electrical Genius‑bus signal to optical signal, extends communication transmission distance for Genius distributed I/O network.
- Provides complete electrical isolation between copper bus segments, suppresses ground‑loop noise and heavy‑industrial electromagnetic interference.
- Transparent repeater device, no PLC software configuration, does not consume Genius bus address resource.
- LED status indication: ‑ Green POWER:Module 24VDC power‑on indicator ‑ Green LINK‑A / LINK‑B:Fiber‑link status for each optical channel ‑ BUS‑ACT:Genius‑bus communication activity indicator
Installation & Wiring Requirements
- Cut off module 24VDC power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling unit.
- Mount IC690RFH008 firmly on panel or DIN‑rail; connect multi‑mode ST fiber cables; connect copper Genius‑bus wiring to electrical terminal ports.
- System wiring strictly follow GE Genius hardware manual; install bus terminator resistor at both physical ends of every copper bus segment; keep fiber path away from high‑voltage / high‑power cables.
- Complete protective grounding according to GE system specification.
- After replacement: power‑on module, verify POWER, LINK‑A/B LED status, perform Genius‑bus scan and full I/O‑loop commissioning test.
- Replacement note: Confirm fiber core cleanliness and ST connector installation; match system Genius baud‑rate; full Genius‑bus‑loop simulation test mandatory before unit put‑into‑service.