GE IC693PWR321 Series 90‑30 Standard 30W Rack Power Supply Module

IC693PWR321 is standard rack power supply for GE Fanuc Series‑90‑30 PLC platform. It must install at the far‑left dedicated power‑supply slot of main baseplate, cannot occupy regular I/O slot. Accepts wide‑range AC or DC main‑source input, provides three regulated DC power rails for backplane bus, relay‑driver circuit and isolated auxiliary 24V. It integrates RS‑485 SNP‑X serial communication port, which is the main serial interface for Series‑90‑30 CPU (CPU350/374 without onboard serial port rely on this port). Built‑in replaceable internal fuse, over‑voltage / over‑current protection. Total rated output power 30W, for small‑to‑medium‑size main rack, not for expansion racks. Expansion racks require separate local power supply. Product status: Obsolete, spare‑part only supply available。

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware & Electrical Specifications

‑ Model:IC693PWR321 ‑ Part Number:IC693PWR321 ‑ Module Type:Series‑90‑30 Standard 30W Rack Power‑Supply Module ‑ Mounting:Far‑left dedicated power‑supply slot on Series‑90‑30 main baseplate only ‑ Input range:  • AC:85‑264 VAC, 50/60Hz  • DC:100‑300 VDC (nominal 125 VDC) ‑ Max input consumption:90VA(AC), 50W(DC) ‑ Peak inrush current:4A / 250ms ‑ Output rails (total 30W):  • +5 VDC backplane logic:15 W, supply CPU & all back‑plane modules  • +24 VDC Relay power:15 W, drive relay‑type output modules (MDL940 etc.)  • Isolated +24 VDC auxiliary:20 W, isolated auxiliary power ‑ Serial port:RS‑485 SNP‑X port on front terminal, for programming, HMI, SNP‑X slave communication ‑ Built‑in protection:Over‑voltage, over‑current, short‑circuit protection; field‑replaceable internal fuse ‑ Memory backup:RTC clock & CPU RAM data backup battery built‑inside power‑supply unit ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ Compatibility note:Cannot install in I/O slot or expansion racks; calculate total 5VDC consumption of all modules inside main rack must not exceed power budget; expansion racks need independent power supply; full rack power‑load check mandatory after replacement。

Environmental Specifications

‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification

Mechanical Data

‑ Weight:approx 0.35 kg ‑ Dimension:Series‑90‑30 standard single‑slot power‑supply form‑factor ‑ Handling note:ESD‑sensitive power circuit; pay attention to internal backup‑battery aging during maintenance; replace fuse only with GE‑specified part number ‑ Terminal tightening torque:0.6‑1.0 N·m

Main Functions

  1. Main rack power source, convert AC/DC field input into 5VDC logic bus, 24V relay‑drive and isolated 24V auxiliary power for main‑base CPU and I/O modules.
  2. Integrated RS‑485 SNP‑X serial port, serves as programming/download and HMI communication channel for CPUs without onboard serial port.
  3. Built‑in battery maintains real‑time clock and CPU RAM data during power‑off condition.
  4. Hardware protective function for over‑voltage, over‑current and short‑circuit fault.
  5. LED status indication on front panel:   ‑ Green OK:Power‑supply normal output indicator   ‑ FAULT:Over‑voltage / over‑current / fuse failure alarm

Installation & Wiring Requirements

  1. Cut off PLC main input power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling power‑supply module.
  2. Insert IC693PWR321 into far‑left dedicated power‑supply slot of main baseplate and lock latch.
  3. Main‑source power wiring strictly follow GE hardware manual; use suitable‑rating wire and external circuit breaker; separate power input cable from signal cables, connect protective ground reliably.
  4. RS‑485 SNP‑X serial wiring: use shielded twisted‑pair, install terminating resistor at bus tail end.
  5. After replacement:power‑on main input, verify OK / FAULT LED status; measure three DC output rail voltage; verify SNP‑X serial communication; calculate total 5VDC load consumption of all plug‑in modules.
  6. Replacement note: Confirm main‑rack total power consumption within 30W rating; expansion racks cannot draw power from this power‑supply; inspect internal backup‑battery health; full‑system power‑on commissioning test mandatory before unit put‑into‑service。

Reviews

There are no reviews yet.