GE IC693PWR322 Series 90‑30 30W DC‑Input Rack Power Supply Module

IC693PWR322 is DC‑input rack power‑supply for GE Fanuc Series‑90‑30 PLC platform. It must be installed in the far‑left dedicated power‑supply slot of main baseplate, cannot be used in I/O slot or expansion racks. Different from IC693PWR321(AC/DC universal input), this model only accepts 24/48VDC field input. Provides three regulated DC outputs for backplane logic, relay drive circuits and isolated auxiliary 24V. Equipped with front‑panel RS‑485 SNP‑X serial port, serves as programming/HMI communication channel for CPUs without onboard serial port. Over‑voltage, over‑current and short‑circuit protection built‑in. Total rated output power 30W, suitable for main rack of small‑medium systems; expansion racks need independent local power supply. Built‑in battery holder for RTC & RAM data backup, battery is not factory‑included. Product status: Obsolete, spare‑part only supply available。

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware & Electrical Specifications

‑ Model:IC693PWR322 ‑ Part Number:IC693PWR322 ‑ Module Type:Series‑90‑30 30W DC‑Input Rack Power‑Supply Module ‑ Mounting:Far‑left dedicated power‑supply slot on Series‑90‑30 main baseplate only ‑ Input range:18‑56 VDC, nominal 24/48 VDC, minimum startup voltage 21VDC ‑ Max input power:50W ‑ Peak inrush current:4A / 100 ms max ‑ Output rails (total 30W combined maximum):  • +5 VDC backplane logic:15 W, supplies CPU & all back‑plane modules  • +24 VDC Relay power:15 W, drives relay‑type output modules  • Isolated +24 VDC auxiliary:20 W, isolated auxiliary power supply ‑ Serial port:RS‑485 SNP‑X port on front terminal, for programming, HMI, SNP‑X slave communication ‑ Built‑in protection:Over‑voltage, over‑current, short‑circuit protection ‑ Memory backup:External lithium battery required for RTC clock & CPU RAM data retention, battery not supplied with module ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ Compatibility note:Cannot install in I/O slot or expansion racks; calculate total 5VDC consumption of all main‑rack modules, must not exceed power budget; expansion racks must use separate power supply; full rack power‑load check mandatory after replacement。

Environmental Specifications

‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification

Mechanical Data

‑ Weight:approx 0.35 kg ‑ Dimension:Series‑90‑30 standard single‑slot power‑supply form‑factor ‑ Handling note:ESD‑sensitive power circuit; battery needs to be purchased separately; check battery aging during maintenance ‑ Terminal tightening torque:0.6‑1.0 N·m

Main Functions

  1. Main‑rack power source, converts field 24/48VDC input into +5VDC logic bus, +24V relay‑drive and isolated 24V auxiliary power for main‑base CPU and I/O modules.
  2. Integrated RS‑485 SNP‑X serial port, serves as program download and HMI communication channel for CPUs without onboard serial port.
  3. Supports external backup‑battery to preserve real‑time clock and CPU RAM data during power‑off.
  4. Hardware protective function for over‑voltage, over‑current and short‑circuit fault.
  5. LED status indication on front panel:   ‑ Green OK:Power‑supply normal output indicator   ‑ FAULT:Over‑voltage / over‑current / short‑circuit alarm   ‑ BATT:Low‑battery warning indicator

Installation & Wiring Requirements

  1. Cut off PLC main DC input power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling power‑supply module.
  2. Insert IC693PWR322 into far‑left dedicated power‑supply slot of main baseplate and lock latch; install external backup‑battery if needed.
  3. DC main‑source power wiring strictly follow GE hardware manual; use suitable‑rating wire and external circuit breaker; separate power input cable from signal cables, connect protective ground reliably.
  4. RS‑485 SNP‑X serial wiring: use shielded twisted‑pair, install terminating resistor at bus tail end.
  5. After replacement:power‑on main DC input, verify OK / FAULT / BATT LED status; measure three DC output rail voltage; verify SNP‑X serial communication; calculate total 5VDC load consumption of all plug‑in modules.
  6. Replacement note: Confirm main‑rack total power consumption within 30W rating; expansion racks cannot draw power from this power‑supply; pay attention to battery health; full‑system power‑on commissioning test mandatory before unit put‑into‑service。

Reviews

There are no reviews yet.

Be the first to review “GE IC693PWR322 Series 90‑30 30W DC‑Input Rack Power Supply Module”

Your email address will not be published. Required fields are marked *