Description
Hardware & Electrical Specifications
- Model:IS200EGDMH1AFF
- Part Number:IS200EGDMH1AFF
- Module Type:Exciter‑Field‑Ground‑Detector Module (EGDM)
- Form factor:Double‑slot plug‑in module for EPBP backplane rack
- Power supply:+12 V / +28 V DC supplied by exciter‑power backplane
- Detection function:Measure field‑circuit insulation resistance, identify AC‑side / DC‑side ground leakage fault
- Interface:P1/P2 backplane connectors, fiber‑optic link to DSPX board; relay fault output contact
- PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance
- On‑board components:High‑voltage capacitors, precision measuring resistors, fault‑output relay
- On‑board protection:Over‑voltage surge suppression, high‑voltage isolation circuit
- Compatibility note:Cannot run standalone; dedicated for GE EX2100 excitation system; jumper / pin setting must match simplex / TMR redundancy mode; full‑function ground‑fault simulation test required after replacement.
Environmental Specifications
- Operating temperature:‑40 ℃ ~ +70 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Excitation control cabinet EPBP rack
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 0.43 kg (1lb 3oz)
- Dimension:228 mm(H) ×152 mm(D) ×38 mm(W) (9″×6″×1‑1/2″)
- Handling note:ESD‑sensitive PCB; contains high‑voltage measuring circuit, anti‑static operation mandatory
- Recommended wire cross‑section:0.75‑2.5 mm² copper cable for field excitation‑monitoring wiring
- Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Apply measuring excitation voltage to generator field circuit, calculate insulation resistance value of field winding and field cables.
- Detect ground‑leakage fault both on AC rectifier side and DC field‑winding side of excitation loop.
- Exchange fault‑diagnosis data with DSPX controller via fiber‑optic communication link.
- Hardware relay output for field‑ground‑fault alarm signal to turbine protection logic.
- Support simplex / TMR triple‑modular‑redundant configuration by backplane pin‑setting.
- On‑board self‑diagnosis: detect module power failure, measuring circuit abnormality, report fault status.
- Front‑panel LED status indication:
- Green LED:Module power supply normal
- Yellow LED:Measuring circuit active, fiber‑link communication ok
- Red LED:Field‑circuit ground‑fault / module hardware fault
Installation & Wiring Requirements
- Cut off exciter‑rack power supply before replacement. Hot‑swap is forbidden. Take anti‑static protection when handling PCB board.
- Insert module fully into designated EPBP rack slot; confirm reliable backplane connector contact.
- Verify backplane pin‑configuration matches system redundancy mode (simplex / TMR).
- Field excitation‑monitoring wiring strictly follow GE EX2100 wiring manual GEI‑100467; separate high‑voltage measuring cables from low‑signal control cables.
- Complete protective grounding according to GE Speedtronic system specification.
- After replacement: perform insulation‑detection calibration, simulate ground‑fault test, verify alarm & trip‑logic response before commissioning.
- Replacement note: Confirm redundancy‑mode pin‑setting; cannot directly swap without function verification.





-1-1-300x300.jpg)